TOPFLEX V-K H05V-K and H07V-K cable has been specially designed for installations that require a flexible cable due to the complex nature of their layout. This cable is specially suitable for domestic wiring. It may also be used for equipment wiring, distributors, cabinets and lighting. It is also recommended for installation under false ceilings. Cables with cross section up to 1 mm2 are especially suited for signalling and monitoring installations.
TOPFLEX V-K H05V-K and H07V-K cable performance
Electrical performance
LOW VOLTAGE 300/500 V
Standard
EN 50525-2-11 / IEC 60227-5
Approvals
HAR / AENOR / CE/ RoHS
CPR Construction Product Regulation
Eca
Thermal performance
Maximum service temperature: 60ºC.
Maximum short-circuit temperature: 150ºC (max. 5 s).
Minimum service temperature: 5ºC.
Fire performance
Flame non-propagation based on UNE-EN 60332-1 and IEC 60332-1.
Reduced halogen emission. Chlorine <15%.
Reaction to fire CPR: E
ca, according to EN 50575.
Mechanical performance
Minimum bending radius: 3 x cable diameter (diameter cable <12 mm2). 4 x cable diameter (diameter cable >12 mm2).
Impact resistance: AG2 Medium severity.
Chemical performance
Chemical & Oil resistance: Good.
Water performance
Water resistance: AD5 Jets.
Other
Meter by meter marking.
Installation conditions
Open Air.
In conduit.
Applications
Mobile use.
Domestic use.
Domestic appliances.
Temporary site installations.
Packaging
Available in rolls (lengths of 50 and 100 m) and drums.
TOPFLEX V-K H05V-K and H07V-K cable design
Conductor
Electrolytic copper, class 5 (flexible), based on EN 60228 and IEC 60228.
Insulation
Flexible PVC.
The standard identification of insulated conductors is the following:
2x Brown + Blue
3G Brown + Blue + Green/yellow
4G Brown + Black + Grey + Green/yellow
5G Brown + Black + Grey + Blue + Green/yellow
Outer sheath
Flexible PVC. Standard colours are grey, white and black. Other colours available on request.